Two safety duties are written into the law for a holiday let in England. The gas appliances and flues you provide must be checked for safety every 12 months by a Gas Safe registered engineer, with a record kept, because the gas regulations cover premises occupied for money under a licence as well as a lease. And because a holiday let for paying guests is not normally occupied as a private dwelling, the Regulatory Reform (Fire Safety) Order 2005 applies: you must carry out a suitable and sufficient fire risk assessment, record it, act on it and keep it under review.
The rules many landlords know from long lets work differently here. The smoke and carbon monoxide alarm regulations and the five-yearly electrical inspection regulations are written for tenancies where someone lives as their only or main home, so they do not reach a holiday booking. The official fire guidance for paying guest accommodation still recommends interlinked smoke and heat alarms, carbon monoxide detectors and an electrical inspection at least every five years. This guide covers England, with a short note on Wales and Scotland. Every rule was read on legislation.gov.uk, GOV.UK and HSE's site on 17 November 2026.
Gas: the yearly check covers holiday lets
The landlord's duties in regulation 36 of the Gas Safety (Installation and Use) Regulations 1998 apply to premises occupied for residential purposes, for money, under a lease or a licence, and where the occupier has a licence the landlord is the licensor. HSE lists the accommodation this covers, including rented holiday accommodation such as chalets, cottages, flats, caravans and narrow boats on inland waterways.
- Every 12 months. Each appliance and flue you provide must be checked for safety within 12 months of being installed and at intervals of not more than 12 months after that (regulation 36(3)(a)). HSE says the check can be done up to 2 months before it is due and keep the original date (when the next check is due)
- By a Gas Safe engineer. The check and any work must be done by, or by an employee of, a member of the class of persons approved by HSE: in practice, a Gas Safe registered engineer (regulation 36(4))
- The record. It must give the date, the address, your name and address, each appliance and flue checked, any safety defect, any remedial action and the engineer's name, signature and registration number, and you keep it until there have been two further checks (regulation 36(3)(c))
- Showing it to guests. A tenant normally gets a copy, but where someone's right to occupy is for 28 days or less, a copy of the record may instead be prominently displayed in the property (regulation 36(6)(b))
- Keeping it safe in between. Every gas fitting and flue must be maintained in a safe condition, not only checked once a year (regulation 36(2))
If a letting agency manages the cottage and its contract gives it the gas duties, HSE says the same duties that apply to a landlord apply to the agent. The gas safety certificate guide covers what the engineer checks.
Fire: the risk assessment is the legal core
The Fire Safety Order does not apply to domestic premises, which it defines as premises occupied as a private dwelling (articles 2 and 6). The Home Office's guide for small paying guest accommodation explains what that means for a holiday let: the law applies if you are charging someone to stay in your property as a guest and it is not being occupied as a private dwelling, even if it is just for one night. Short stays by guests who are not friends or family make it unlikely the property counts as a private dwelling.
Who is responsible. The responsible person is whoever has control of the premises in connection with a business, or otherwise the owner (article 3). The guide says this is likely to be the owner, a letting agent, or another person in control. Your local fire and rescue service normally enforces it.
What the law asks. The responsible person must make a suitable and sufficient assessment of the fire risks to the people on the premises (article 9(1)) and, since 1 October 2023, must record it, including the findings, the measures taken or to be taken and any group of people identified as especially at risk (article 9(6) and (7)). It must be reviewed regularly, and especially after a significant change (article 9(3)); the guide says an annual review is usually appropriate.
Which guidance to follow. GOV.UK's page for holiday home owners in England says you must follow the guide for small paying guest accommodation where it fits, or the national sleeping accommodation fire safety guidance for larger or more complex properties. The small guide covers a house, cottage or chalet with a ground floor, or ground and first floor, sleeping no more than 10 people with no more than four bedrooms on the first floor, and individual flats. It uses "must" for what the law requires and "should" for its recommendations. You can carry out the assessment yourself if you feel able to, or use a competent fire risk assessor, whose name you should record; either way the responsibility stays with you (fire risk assessment).
Smoke, heat and carbon monoxide alarms
The Smoke and Carbon Monoxide Alarm (England) Regulations 2015 apply to a specified tenancy, which they define as one that gives the occupier the right to live in the property as their only or main residence. A holiday booking is not that, so the regulations themselves do not apply. The Fire Safety Order does: where necessary to keep people safe, the responsible person must ensure the premises have fire detectors and alarms to the extent appropriate (article 13). The small paying guest guide sets out what it normally expects:
- Interlinked alarms. Interlinked domestic smoke and heat alarms should be provided in all areas where a fire might start, so that when one detects a fire they all sound. Smoke alarms in hallways, corridors, staircases, lounges, dining rooms and bedrooms; heat alarms in every kitchen and in rooms such as utility rooms where steam or fumes would set off a smoke alarm
- Mains powered. Alarms should be mains powered, with a standby battery protected from tampering, known as Grade D1. Long-life sealed battery alarms (Grade F1) may be acceptable as a short-term measure, for around 2 to 3 years, until a D1 system is fitted
- Carbon monoxide. Carbon monoxide detectors should be provided where the accommodation contains a gas or solid fuel-burning appliance
- Replacement. Smoke alarms typically last about 10 years
GOV.UK's page for holiday home owners also points to the government's smoke and carbon monoxide alarm booklet for landlords.
Electrics: what applies to a holiday let
The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, which require a landlord to have the installation inspected and tested at least every five years, also apply only to a specified tenancy: one that gives the occupier the right to live there as their only or main residence (regulation 2). A holiday booking is outside them.
Electrical safety is still part of the holiday let's duties. GOV.UK's page for holiday home owners in England says you must follow HSE's guidance on electrical safety and the government's guidance on electrical safety standards in rented homes. The small paying guest guide is more specific:
- The wiring. You must make sure your electrical wiring has been checked by a qualified contractor, and look out for damaged cables and cracked or loose sockets
- Every five years. The electrical installation should be inspected and tested at least every five years, and any work on it done only by a competent electrical contractor. That is the same interval the 2020 regulations set for a long let, where the installation must be inspected and tested at intervals of no more than 5 years (regulation 3(2))
- Appliances. Appliances should be checked regularly in line with the manufacturer's instructions, registered with the manufacturer and checked against recall lists, with a visual check that each appears in good condition between lets
- Extension leads. Extension cables, trailing leads and adaptors should be avoided wherever practicable
Heating, furniture, candles and the way out
The same guide covers the hazards a holiday let has and a long let often does not:
- Gas cooking and heating. Gas appliances must be checked and serviced annually by a Gas Safe registered engineer, and heating and hot water systems should be maintained every year by a qualified contractor. Portable heaters should be avoided where possible
- Open fires and log burners. A fire or spark guard should be provided and the chimney swept at least once a year, with ash bins and instructions for guests
- Candles. You should not provide candles, tea lights or ethanol burners for guests, and should have a policy against their use
- Furniture. Furniture and furnishings you provide should comply with the Furniture and Furnishings (Fire) (Safety) Regulations 1988
- Exits. Front and back doors must not need a key to unlock them from the inside, and escape routes must be kept clear
- Lighting. Where guests would have to find their way out in the dark if the power failed, emergency escape lighting must be provided where it is needed for their safety; in the smallest premises, rechargeable torches that light when the power fails may be acceptable
- Firefighting equipment. Guests are not expected to fight a fire, but in self-catering accommodation you may wish to provide a small extinguisher or a fire blanket in the kitchen
- The escape plan. Guests do not know the building. The guide suggests a simple plan on the back of the bedroom door and in the welcome pack, with how to call the emergency services and how to describe where the property is, especially if the postcode may not find it
The checks, by the year and by the changeover
| When | What | Where it comes from |
|---|---|---|
| Every 12 months | Gas safety check and record by a Gas Safe engineer | Gas regulations, regulation 36 |
| Every 12 months | Review of the fire risk assessment, and after any significant change | Fire Safety Order, article 9; the guide |
| Every 12 months | Chimney swept; heating and hot water maintained; emergency lighting and extinguishers serviced | The guide |
| At least every 5 years | Electrical installation inspected and tested | The guide |
| Each changeover | Smoke and heat alarms tested; exit doors open easily; torches or emergency lights work; appliances look sound | The guide (weekly and monthly tests at each change of occupancy in self-catering premises) |
| About every 10 years | Smoke alarms replaced | The guide |
The guide asks for a record of testing and maintenance, in a log book or kept electronically.
EPCs and the registration scheme
GOV.UK's page for holiday home owners in England says you must check whether you need an energy performance certificate, and links the government's guidance on EPCs for letting. It also says the government is introducing a mandatory national registration scheme for short-term lets in England, which it expects to begin in March 2027. That scheme is not yet in force. If you later let the cottage to a tenant as their home, the tenancy rules on alarms and electrical reports do apply, along with the rest of a long let's set-up (from holiday let to long let).
Wales and Scotland
- Gas. Regulation 36 of the gas regulations extends to England, Wales and Scotland, so the yearly check applies in all three
- Fire. The Fire Safety Order covers England and Wales, but the small paying guest guide applies only to England: the guide says separate guidance applies in Wales, and that different fire safety law applies in Scotland
- Scotland's licence. In Scotland you must get a short-term let licence from the council before you take bookings or host guests in self-catering accommodation (mygov.scot; short-term let licence)
Every date and record for the cottage in one place
The dates kept, and the reminders sent. LetCompliance does not take bookings or plan the cleaning; it keeps each property's safety records and the people who do the work. On every plan, the cottage's gas safety record, electrical report, fire risk assessment and smoke and carbon monoxide alarm check are kept with their dates, an uploaded certificate has its dates read for you to confirm, and a reminder email goes out 90, 30, 14, 7 and 1 days before each one runs out. On the maintenance board you log each alarm test and keep planned servicing, such as the chimney sweep and the boiler service, with its own reminders. On the trial and paid plans, your contractors are kept with their Gas Safe numbers, and a job goes to them with the quote to approve and the cost recorded. The same account holds the money and the tax figures for the cottage and any long lets you own. Single, for one property, is £7.99 a month.